Make up air W/ Devin Skipper

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

Devin Skipper comes on the podcast to give you an introduction to make-up air systems and explain their purpose. This time, we pull out all of the initials: MAU, MUA, DOAS, and MHGRV.

Make-up air is outdoor air that we bring in to replace exhausted indoor air, usually in commercial systems. We use dedicated systems to bring in humidity-controlled air to rebalance the building to a positive pressure; hotels, restaurants, and medical facilities with significant exhaust need fresh air to compensate for that exhaust and negative pressure. Unsurprisingly, design is critical for these systems, especially in humid climates.

For example, in a restaurant, fresh air must come in from an area where it can add positive pressure without too much humidity. So, exhaust devices AND make-up air units will be on the roof. Undesirable infiltration occurs through cracks and under doors and usually isn’t enough to make a satisfactory difference in the building pressure. In commercial facilities, excess negative pressure can make it difficult for people to open doors, which could present a safety hazard for building occupants.

MHGRVs (modulating hot gas reheat valves) modulate discharge gas through a reheat coil. These components allow a system to keep running and maximize dehumidification without overcooling the space. When a reheat valve opens, the condenser valve closes and redirects discharge gas to the reheat coil, but they are NOT the same parts that facilitate hot gas defrost. These also keep systems from tripping on high head pressure.

Devin and Bryan also discuss:

  • High-latent markets and design conditions
  • Measuring pressure (in wc)
  • Excess positive pressure complications
  • Floor drains and negative pressure
  • Reheat strategies
  • MUA fans vs. units
  • MUA controls

Learn about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

The Fuse Only Blows When You Leave – Short #307
Questionable CO Alarms w/ Bill Spohn
Same Charge, Different Numbers – Short #306
Tech, Mechanic, or Craftsman? Finding Your Fit in HVAC
Normal Subcooling, Hidden Restriction – Short #305
Airflow Serenity w/ Alex Meaney
Less Compressor, More Suction Pressure – Short #304
Mastering Your Meter Advanced Functionality with Louise Kellar (UEi Test Instruments)
Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from