Glycol Skids for Market Refrigeration w/ Max Johnson
Make & share a podcast clip
Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.
Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

Glycol secondary loop systems are showing up in more and more grocery stores, and in this episode of the HVAC School Podcast, Bryan Orr sits down with Max, one of the company’s lead startup techs and its in-house subject matter expert on glycol skids. Max explains what these systems are, why clients are choosing them for retrofits, and what it takes to commission one without taking a live store down. The big picture: a traditional DX rack chills a water and propylene glycol mix in a heat exchanger, and that glycol is pumped around the store to cool the medium-temperature cases.
The conversation starts with the “why.” Reduced refrigerant charge inside the building, keeping flammable or higher-GWP refrigerants out of the sales floor, regulatory pressure, and zero-emissions initiatives all push clients this way. Max is upfront that efficiency isn’t one of the reasons at this scale, since the extra heat exchange step, lower suction temperatures, and pump energy all cost something. He also covers the trade-off in reliability: case-level controls are simple, but a fault in one of the skid’s main valves can take out every case at once, so techs have to move fast.
From there, Max walks through the skid itself, from the brazed plate heat exchanger, VFD-controlled pumps, and air separator to the expansion tank, strainers, suction guide, controller, and EEV drivers. He then covers flow control with balance valves, defrost strategy, and the importance of proper vents and drains in the piping. The two get into the details of startup and commissioning, and some key takeaways include pressure testing instead of pulling a vacuum, filling and purging air, and verifying that the refrigerant-side valves are wired and driven correctly so a swapped valve doesn’t flood the rack.
The back half of the episode is practical field advice. Max shares how to recognize air in the loop, why store humidity and dew point matter so much for case performance, which specialty tools and fittings he carries, and how to handle glycol mixing and top-offs.
Topics Covered
- What a glycol secondary loop system is, and how it differs from direct expansion
- Why retrofits are happening: refrigerant charge reduction, safety, EPA regulation, and zero-emissions goals
- Efficiency penalties at small scale, and why efficiency isn’t the driver
- How glycol behaves in the coil: no latent exchange, a temperature gradient, and frost patterns
- Reliability trade-offs: simple case controls versus centralized, mission-critical valves
- Staging a retrofit so the store stays open, including pre-piping, pre-testing, and pipe cleaning
- Brazing versus soft solder, and whether nitrogen flow matters with glycol
- Skid components: heat exchanger, VFD pumps, air separator, feeder tank, expansion tank, strainers, and suction guide
- Controller inputs, EEV drivers, and emergency mobile chiller connections
- Balance valves (automatic versus manual) and defrost methods, including off-time and electric
- Fluid distribution: pitching pipe for air and drainage, plus vents and drains
- Propylene versus ethylene glycol, the 35% mix, freeze point, and why more glycol hurts heat transfer
- CO2 as a secondary fluid for low-temperature applications
- Commissioning steps: electrical checks, pressure testing, filling, purging, and testing valve operation
- Proving performance: flow, glycol concentration, temperature, and superheat on the rack side
- Troubleshooting air in the system and pressure changes as glycol chills
- Store humidity, dew point targets, and case performance
- Heat reclaim using glycol loops
- Tools: PT ports, manometers, female-to-female hoses, refractometer, and transfer pumps
- Service tips: distilled water, matching glycol brands, and glycol safety
This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, and Filtrete.
Resources
Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.
Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.
Discuss this reference → Related forum discussionsAuthor:
Comments
To leave a comment, you need to log in.
Log In