In this short podcast episode, Bryan talks about electric heat and whether your service or maintenance procedure actually allows you to test every heat strip. In our climate, we use electric heat as auxiliary heat (as opposed to a furnace in a dual-fuel setup). There is also some information about maintenance procedures, blower interlocks and relays, and math to determine amperage.

If you put the thermostat in heat and the blower runs, you only prove that the heat pump is heating; it doesn’t tell you which electrical circuit is heating, or whether the auxiliary heat is producing heat at all. You can’t assume that the last tech left you the correct kit with everything wired up and that it has been wired properly with the correct wire size.

Electric heaters in heat pumps usually turn on with a W call from the thermostat or the defrost board. Sometimes, there is a high-voltage interlock with a relay that runs the blower with the electric heat but not the other way around. Older heat strips may also have heat sequencers, which follow a specific sequence and stage on or off over time.

We test heat strips by forcing a call for heat, waiting as long as needed, measuring the amperage to make sure it matches the heat kit, making sure the blower comes on, and verifying that the call for heat ends as it’s supposed to. Temperature rise may also be a useful measurement. If a similar procedure is part of your fall maintenance, let the customer know that there may be an odor, and you may clean dirty heat strips with compressed air or an electrical contact cleaner.

The key takeaway is to make sure the amperage is correct and that the circuit’s wiring and relays can safely carry the current. Don’t assume that everything is correct when you work on a unit for the first time.

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Copeland, and Santa Fe Dehumidifiers.

Resources

 

Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Uncovering the Root Causes of Commercial Refrigeration Failures
Why and How to Test Heat Pump Defrost – Short #310
Building a Business That Lasts: Why Culture Beats Strategy in HVACR w/ Tony Gonzalez
Tight Enough to Fail – Short #309
Glycol Skids for Market Refrigeration w/ Max Johnson
Your Thermostat Is Reading the Wall – Short #308
Next-Gen Filtration – Pressure Drop, MERV 16, and Bypass Prevention w/ Chris Howells
The Fuse Only Blows When You Leave – Short #307
Questionable CO Alarms w/ Bill Spohn
Same Charge, Different Numbers – Short #306

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from