The Fuse Only Blows When You Leave – Short #307

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast episode, Bryan talks about the fuse that only blows when you leave. The service call usually goes like this: you replace a blown fuse, the system runs fine, you leave, and then the fuse blows again. There could be several causes of a blown fuse.

First, ask what was happening right before the system stopped, such as if the unit was starting up, if it was raining outside, or if the operating mode changed. The customer may not know the specifics, but they may be able to offer a clue. If the control fuse blows during a specific call, we may be able to locate a short in one of the circuits involved. We may also be able to find out a bit by inspecting places where wire often gets damaged, such as common points where conductors pinch or rub.

Isolation diagnosis can help us isolate the specific circuit or component with a problem. First, look at the wiring diagram, label conductors, and take pictures of the original setup before disconnecting anything. Keep the correct fuse protection instead of using a larger fuse, leave all safety controls in the circuit, and use the manufacturer’s test procedure if it’s available. Then, isolate different loads and conductors so they can be energized individually; some modern thermostats make this easy. Also note that continuity testing alone isn’t always reliable for locating problematic paths.

Sometimes, motion (from motors), temperature, and moisture can also contribute to intermittent issues. Additionally, some inductive loads, like contactor coils, experience unique intermittent issues that cause the components to draw high current; inductive reactance matters. Measuring current on the different circuits as you energize them can also point you toward circuits that have higher current than expected.

Once you’ve found and repaired something, go back to the condition that made it fail. Make sure you fix the underlying problem, such as exposure to excess heat, vibration, or moisture.

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, Fieldpiece, TruTech Tools, and Filtrete.

Resources

 

Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Questionable CO Alarms w/ Bill Spohn
Same Charge, Different Numbers – Short #306
Tech, Mechanic, or Craftsman? Finding Your Fit in HVAC
Normal Subcooling, Hidden Restriction – Short #305
Airflow Serenity w/ Alex Meaney
Less Compressor, More Suction Pressure – Short #304
Mastering Your Meter Advanced Functionality with Louise Kellar (UEi Test Instruments)
Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from