In this short podcast, Bryan covers three things that the condenser does. He also explains where those things happen and what those they mean in terms of system operation.

The evaporator coil does two things: boiling and superheating. However, a condenser does three things: desuperheating, condensing (changing state), and subcooling.

Desuperheating occurs early on in the condenser, at the top. Refrigerant enters the condenser as a highly superheated vapor. Even though we have a few degrees of superheat in the suction line, the discharge line’s superheat is a lot greater. (For context, the suction line will feel cold to the touch, but the discharge line will burn you.) The compressor skyrockets the superheat through the heat of compression and sends that refrigerant to the condenser via the discharge line. So, desuperheating reduces the temperature from 160+ degrees to the saturation temperature, about 100 degrees.

In the middle of the condenser coil, the refrigerant stays at saturation. However, it continues rejecting heat. That is because the refrigerant is undergoing a phase change from vapor to liquid; it rejects heat in the form of latent heat even though the temperature stays the same. Once all of that latent heat has been rejected to the air, the refrigerant becomes fully liquid. Then and only then can the refrigerant start to drop its temperature.

The temperature of the liquid refrigerant drops at the bottom of the condenser coil. We call that process subcooling. Subcooling refers to the temperature of a liquid below the saturation point. For example, if the saturation point is at 100 degrees but the liquid refrigerant is 95 degrees, you will have 5 degrees of subcooling. In general, a common subcooling range is 8-14 degrees.

Learn more about Refrigeration Technologies at refrigtech.com.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani
Behind the Drywall – The Psychrometrics of a Hidden Moisture Failure – Short #298
HVAC Education. What NOT to Do w/ Jim F., Roman B. and Craig M.

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from