In this podcast episode, Bryan goes over best practices for diagnosing and replacing an A/C or refrigeration compressor. 

When testing for a shorted compressor, make sure the compressor is isolated from all of its circuitry. You would see low ohms to ground in a shorted compressor. Do NOT measure from winding to winding or terminal to terminal to diagnose a short.

You may also come across an open winding failure. In the case of an open compressor, the power is going to the compressor, but it’s not doing anything. 

Locked compressors also go out on internal overload and draw high amps. Try your best to unlock the compressor but be realistic about the state of compressor health.

Poor compression also indicates a failure. You would typically see low head pressure and high suction pressure with low system capacity.

When replacing the compressor, you’ll want to start off by knowing the type of failure that was diagnosed. Reconfirm the diagnosis. Then, do your acid test and make sure you have a matching capacitor and enough refrigerant to do the job. Know your connection types, compressor model, and warranty status.

Fully recover the old refrigerant charge and remove all existing driers in the system. Braze in the new compressor and pressurize the lines with nitrogen. Bubble-test all new joints and check them thoroughly. Then, pull your vacuum before adding charge by weighing a factory charge into the liquid line.

When you power on the unit, monitor the performance and inspect the unit closely.

Bryan also discusses:

  • Clarification on flowing nitrogen
  • Learning theory vs. application
  • Pulling terminals off
  • Proper megohmmeter use
  • “Redneck” test (running the system without the compressor)
  • Acid and oil testing
  • Hard start kits and oil migration
  • Accumulators and acid protocols
  • Suction line driers
  • Mufflers
  • Vacuum pump oil

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Comments

dustin
dustin @bryanorr

Bryan, is there any chance you have these steps layed out in anything like a checklist format. I’d love to use it when training.

6/28/17 at 11:33 AM

Bryan, is there any chance you have these steps layed out in anything like a checklist format. I’d love to use it when training.

Files:
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani
Behind the Drywall – The Psychrometrics of a Hidden Moisture Failure – Short #298
HVAC Education. What NOT to Do w/ Jim F., Roman B. and Craig M.
Q&A What Uninsulated Refrigerant Lines Really Cost You – Short #297

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from