In this short Q&A podcast episode, Bryan answers a question about drain traps and static pressure. This question was sent by Stephen with The Comfort Squad when he noticed an uptick in nuisance calls on retrofit systems that kept having their secondary drain pans filled.

In negatively pressurized systems (i.e., straight-cool or heat pump units, not gas furnaces), air can pull water back into the drain line. The evaporator coil is under negative pressure because the blower is on top of the evaporator coil.

The rule of thumb for trap depth is that it should be greater than or equal to twice the return static pressure (which is why a 1″ deep trap is typical for systems with 0.5″ return static pressure). However, return static can have some variation, and it’s also not a great idea to use the TESP for this measurement because the return static could be greater than the supply. It makes most sense to account for the highest possible return static you will see.

1″ is only sufficient if 0.5″ return static pressure is the most you will see, so bigger is usually better in all cases. If you can install a 2″ or 3″ trap, you’ll typically have your bases covered without having an excessive trap.

We also wrote a tech tip about this topic: https://hvacrschool.com/drain-trap-depth-and-negative-pressure/

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://www.hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Did You Actually Test Every Heat Strip – Short #311
Uncovering the Root Causes of Commercial Refrigeration Failures
Why and How to Test Heat Pump Defrost – Short #310
Building a Business That Lasts: Why Culture Beats Strategy in HVACR w/ Tony Gonzalez
Tight Enough to Fail – Short #309
Glycol Skids for Market Refrigeration w/ Max Johnson
Your Thermostat Is Reading the Wall – Short #308
Next-Gen Filtration – Pressure Drop, MERV 16, and Bypass Prevention w/ Chris Howells
The Fuse Only Blows When You Leave – Short #307
Questionable CO Alarms w/ Bill Spohn

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from