Q&A – System Won’t Dehumidify? – Short #214

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast episode, Bryan answers a listener-submitted question about an HVAC system that won’t dehumidify. This question was submitted by a homeowner with a Carrier heat pump with an attic air handler that cools but won’t dehumidify on the hottest days of summer. One of the past companies that serviced the system added charge, but the problem wasn’t resolved.

This case doesn’t seem to be a sizing issue, as the insufficient dehumidification is happening on the hottest days. Normally, sizing issues happen during the edge seasons when temperatures aren’t as high as in the summer, but the dew points are still high.

Bryan’s first recommendation is to use measureQuick to evaluate the delivered capacity and determine the sensible heat ratio (SHR) by comparing sensible BTUs to latent BTUs. High SHRs are associated with less effective dehumidification and more effective sensible BTU removal.

Then, we have to determine that airflow is properly dialed in. Typically, lower fan speeds are associated with better dehumidification; 350 CFM per ton is typical of humid climates. In the case of two-speed or variable-speed equipment, we should verify that it is staging up and down properly.

On the ventilation side, a duct leakage test is recommended. Proper use of exhaust ventilation, like bath fans and kitchen exhaust, is also critical. Structural leakage and MAD-AIR are also worth checking if a company can measure those, though those are premium services that are usually more expensive.

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 6th Annual HVACR Training Symposium at https://www.hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Uncovering the Root Causes of Commercial Refrigeration Failures
Why and How to Test Heat Pump Defrost – Short #310
Building a Business That Lasts: Why Culture Beats Strategy in HVACR w/ Tony Gonzalez
Tight Enough to Fail – Short #309
Glycol Skids for Market Refrigeration w/ Max Johnson
Your Thermostat Is Reading the Wall – Short #308
Next-Gen Filtration – Pressure Drop, MERV 16, and Bypass Prevention w/ Chris Howells
The Fuse Only Blows When You Leave – Short #307
Questionable CO Alarms w/ Bill Spohn
Same Charge, Different Numbers – Short #306

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from