Superheat in Heat Mode: Why Heat Pumps Get Weird – Short #274

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast, Bryan answers a listener-submitted question and explains why heat pumps get a bit weird: when it comes to superheat in heat mode. He also explains how we can move heat from outdoors to indoors, even in temperatures below freezing (cold temperatures just have less heat, not zero heat).

In order to move heat in very cold conditions, we need very low suction pressures and cold coils, which gives us a high compression ratio. Superheat will be affected by these conditions. Remember: superheat that is too low can cause floodback, and superheat that is too high can cause the compressor to overheat.

Superheat is easy to check in cooling mode, but it’s harder in heating mode, especially since the suction line is at the outdoor unit. In heating mode, we can only measure superheat between the coil outlet and the reversing valve inlet, which is a very short run of tubing.

The superheat will also be less stable in heat mode in cold weather, and it will have a wider range of “normal” values than cooling mode, depending on the conditions. Superheat could even drop to zero with some fixed-orifice metering devices (which would cause floodback). That’s why many of these heat pumps have accumulators, which collect liquid refrigerant to protect the compressor. Even though TXVs attempt to maintain superheat, you may still see some variation in heat mode during cold weather. EEVs are common in ductless systems and are highly controllable but maintain relatively low superheats by design; fast metering control, intelligent logic, accumulators, and low refrigerant charges allow them to avoid floodback in low temperatures.

In any case, spikes and drops in temperature can cause the superheat to jump or collapse because the load changes (as the outdoor coil is the evaporator). Frost buildup on the coil also inhibits airflow and heat transfer, causing the superheat to change as the evaporator pressure and temperature drop. Defrost also introduces chaos to the equation. All of these should influence your judgment when checking superheat to diagnose or commission a system in heat mode.

 

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 7th Annual HVACR Training Symposium at https://www.hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from