Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast, Bryan and Roman discuss premature coil failure in ductless mini-splits and VRF equipment.

These coils are susceptible to a few different types of corrosion. Warmer coil saturation temperatures and shorter runtimes result in lower latent capacity; whatever moisture is on the coil dries on the coil instead of draining out. Minerals and chemicals (including chlorides from bleach or cleaners) interact with the coil and may cause corrosion, including formicary (“ant’s nest”) corrosion. Leaks and corrosion may be environmental rather than entirely attributable to manufacturer defects.

Technicians can use proper cleaners with correct dilution ratios and rinse the coils. In situations where the environment contributes to coil corrosion, such as with substances off-gassing or dealing with coastal air, we will need to dilute the pollutants by ensuring proper ventilation. Dilution needs to be intentional, especially in hot-humid climates, and ventilating dehumidifiers with good filtration may be a good move. Source control and filtration are also good mitigation strategies, and clear, open client communication can help clients understand the problem and make informed decisions about their HVAC system.

This episode contains embedded sponsor messages from Refrigeration Technologies, Carrier, NAVAC, and Fieldpiece.

Resources

Purchase your tickets or learn more about the 8th Annual HVACR Training Symposium at https://www.hvacrschool.com/symposium.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300
Tips for Being On Call w/ Ty
The Florida “M-Word” – Legal Boundaries & Tech Communication – Short #299
Becoming a GRIT Host or Mentor w/ Leilani
Behind the Drywall – The Psychrometrics of a Hidden Moisture Failure – Short #298

Author:

The HVAC School site, podcast, and tech tips are
made possible by generous support from