Disappearing Latent Capacity – Short #95

Make & share a podcast clip

Keep the exact passage and a link to the full episode. Choose up to three minutes, with enough context to be fair to the speaker.

Preview uses this episode’s audio. Browser audio export, when supported, takes the length of the selected clip. Nothing plays until you choose Preview.

In this short podcast, Bryan explains why latent capacity is prone to disappearing. He also explains what actually happens when the latent capacity drops.

When you measure enthalpy split across the coil, you’ll learn that the equipment design makes it perform to AHRI design conditions. Those design conditions are 95-degree outdoor temperature and 80-degree indoor temperature at 50% indoor relative humidity. So, the A/C system must remove a lot of moisture. However, we don’t usually run A/C units for 80-degree indoor temperatures; we usually aim for a 75-degree indoor temperature. When we have 80 degrees, the sensible AND latent heat loads are higher. Things get tricky when we encounter disappearing latent capacity, which is when you remove less moisture.

If we have equipment with a sensible heat ratio (SHR) of 0.75 at design conditions, we’ll likely have a higher SHR with our typical conditions. When the dew point is lower, water condenses on the evaporator coil at a lower temperature; water holds up the surface temperature of the evaporator coil and optimizes heat removal, suction pressure, and compression ratio. When heat transfers to the water on the coil, the sensible heat in the air decreases via a latent process.

When we don’t have moisture on the coil, all of the heat going from the air into the refrigerant is making it in via conduction through the metal coil walls. Unless the coil gets below the dew point, it won’t remove any moisture; we can still remove sensible heat, but you don’t have the advantage of the moisture “holding up” the surface temperature.

In very dry climates, we increase the airflow because we don’t want to remove moisture from the air, but we still want heat to be available to the evaporator coil. However, we have to be careful about the bypass factor.

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Work through this with the trade.

Highlight a short passage, or bring a question about a specific moment into HVAC No Bull Forum.

Discuss this reference → Related forum discussions

Comments

Airflow Serenity w/ Alex Meaney
Less Compressor, More Suction Pressure – Short #304
Mastering Your Meter Advanced Functionality with Louise Kellar (UEi Test Instruments)
Premature Coil Failure in Ductless Mini-Splits & VRF Equipment – Short #303
Advanced Refrigerant Recovery: Best Practices for Diverse Systems and Environments
The A2L & Refrigerant Transition – Short #302
Invented For Techs, by Techs: Inside Refrigeration Technologies’ “The Lab”
The Ethics of IAQ – Testing vs. Remediation Conflicts – Short #301
Is 400 CFM per Ton Always Right? w/ Ty
The MERV 15 Filtration Physics – Short #300

Author:

To continue you need to agree to our terms.

The HVAC School site, podcast, and tech tips are
made possible by generous support from