In this short podcast episode, Bryan talks about the placement of the TXV sensing bulb. He also explains how it affects the opening force on the TXV.

The TXV sensing bulb (or sensor on an EEV) provides the opening force for the valve. The warmer the bulb gets, the more the valve opens; the colder the bulb gets, the more the valve closes. The TXV also has a closing force provided by the spring pressure and equalizer (usually the external equalizer).

So, if you have a bulb that has been poorly mounted or insulated, you tend to have more opening force than the design. Your suction line will generally be colder than the airstream around the evaporator coil. If the sensing bulb has poor contact with the suction line, it will likely read warmer temperatures than it should.

When the TXV opens more than it should, the valve loses control and could lead to flooded conditions. (If that liquid gets to the compressor, then you could get catastrophic damage.) Generally speaking, improper TXV bulb placement will result in low superheat and potential flooding. When you have a high superheat or a starved evaporator, the sensing bulb placement is rarely the actual problem.

When mounting a sensing bulb, the suction line should be clean. Get rid of all Armaflex residue and ensure that the bulb is also clean. In some cases, you may need to insulate the bulb. You must also ensure that you mount the sensing bulb securely near the evaporator outlet, and you can be a few inches downstream of the external equalizer. Another common suggestion is to place the bulb on top of the line if the line is smaller than 7/8″ (larger than 7/8″, you can mount the bulb at 4 o'clock or 5 o'clock on the line).

Learn more about Refrigeration Technologies HERE.

If you have an iPhone, subscribe to the podcast HERE, and if you have an Android phone, subscribe HERE.

Comments

Succession in Family Business w/ TruTech & Kalos
Adding Plumbing To Your HVAC Business – Short #282
Troubleshooting Tips and Tricks w/ Let’s Be Techs
Heat In….Heat Out: All About Heat Transfer w/ Joe Joe The HVAC Man – Short #281
Building Science at the Kitchen Table: Using Testing to Close the Sale
Hard Lessons w/ Roman, Tim D., Nathan O. and ELK
Better Seen than Viewed w/ Jim Bergmann
Symposium – What Good Techs Do Different W/ Data
Heat Recovery from Data Center w/ Jeff Staub
All About ESCO with Renee Tomlinson and MeasureQuick’s Latest Features with Jim Bergmann

Author:

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and tech tips
made possible by generous support from