Sizing Breakers and Conductors (for HVAC) – Have Things Changed?

In this essential episode, Bryan Orr sits down with Elliot, the residential install supervisor at Kalos Services, to unpack a critical issue that's causing confusion among HVAC technicians, electricians, and inspectors alike: the new standards for breaker and conductor sizing on inverter-driven equipment. The conversation was sparked by Elliot's frustrating experience of having two inspectors in the same county fail the same installation for opposite reasons—one for an oversized breaker and another for an undersized breaker. This contradiction led to a deep dive into recent changes in UL standards and how they affect everyday HVAC installations.

The heart of the issue stems from the transition to low-GWP refrigerants and the updated UL 60335-2-40 Edition 3 standard, which replaced the 1995 certification approach. This new standard introduced more conservative calculations for electrical characteristics, particularly affecting equipment using A2L refrigerants. The result? Data tags now show higher Minimum Circuit Ampacity (MCA) ratings than before, even though the equipment itself hasn't changed—only the math used to calculate these values has shifted. This has created a puzzling situation where the MCA can be higher than the recommended breaker size, which seems counterintuitive to anyone familiar with traditional electrical principles.

Bryan and Elliot clarify the fundamental rule that still applies: size your wire to the MCA and your breaker to the MOCP (Maximum Overcurrent Protector). The confusion arises because manufacturers like Mitsubishi are now including “recommended breaker” sizes on data tags that are lower than the MCA—a courtesy to contractors, not a code requirement. The higher MCA reflects conservative safety margins that account for extreme operating conditions, but in practice, inverter-driven systems have multiple built-in protections that prevent them from ever actually reaching these calculated amperage levels. The key takeaway is that contractors can safely install breakers at the recommended size without safety concerns, as long as the breaker's lugs are rated to accept the wire size required by the MCA.

The episode also explores how inverter-driven equipment fundamentally differs from traditional PSC motors, particularly regarding locked rotor amps (now more accurately termed “inverter input”) and voltage drop considerations. Unlike conventional motors that simply run slower with reduced voltage, inverter-driven compressors and ECM motors compensate by drawing more current to maintain performance, creating a potential compounding effect with voltage drop that installers need to understand—even though voltage drop itself isn't an enforceable NEC code requirement.

Topics Covered:

  • New UL 60335-2-40 Edition 3 standards and their impact on electrical calculations for HVAC equipment
  • The relationship between MCA (Minimum Circuit Ampacity) and MOCP (Maximum Overcurrent Protector) and why they can now seem contradictory
  • Recommended breaker sizes on modern data tags and why they may be lower than the MCA
  • Handling inspector conflicts and failed inspections related to breaker sizing
  • Differences between inverter-driven equipment and traditional PSC motors in electrical behavior
  • The transition from “locked rotor amps” to “inverter input” terminology for modern equipment
  • Voltage drop considerations with inverter-driven systems (NEC 210.19A and 215.2A)
  • Why inverter-driven equipment draws more current at lower voltages compared to traditional motors
  • Proper wire and breaker sizing for A2L refrigerant equipment (454B systems)
  • NEC Section 440 requirements specific to air conditioning and refrigeration equipment
  • Breaker lug ratings and ensuring they can accept the required wire size
  • Practical advice for communicating with inspectors and resolving code disputes

 

Read the tech tip on this topic HERE.

Have a question that you want us to answer on the podcast? Submit your questions at https://www.speakpipe.com/hvacschool.

Purchase your tickets or learn more about the 7th Annual HVACR Training Symposium at https://hvacrschool.com/symposium.

Subscribe to our podcast on your iPhone or Android.

Subscribe to our YouTube channel.

Check out our handy calculators here or on the HVAC School Mobile App for Apple and Android.

Comments

Absorption Cooling – The Rise and Fall and Rise – Short #272
Combustion Analysis w/ Tony G.
Residential vs. Commercial HVAC Sales
When Ammonia Ruled the World – Short #270
Humidity, Airflow, and Refrigeration
The Finned-Tube Coil – Short #269
Are Two Are Better Than One: Understanding Tandem Compressors
The Tech That Tried to Beat the Compressor – Short #268
VRF, Ductless and Humidity Control w/ Roman
The History of the Thermostat – Short #267

Author:

loading

To continue you need to agree to our terms.

The HVAC School site, podcast and tech tips
made possible by generous support from