Refrigeration Circuit, Charging & Diagnosis
Suction Accumulators A suction accumulator is used to prevent liquid refrigerant floodback to the compressor. A compressor is designed to move vapor refrigerant, NOT liquid, and the accumulator can really help us win that battle. Accumulators are commonly used on heat pumps, transportation refrigeration systems, low-temp supermarket systems, and any place where liquid refrigerant flooding […]
Read more
In commercial HVAC, you will find several different types of multi-stage evaporator coils: intertwined (shown above), horizontal face split (one coil on top of another), and vertical (side by side). When staging a horizontal evaporator, pay attention to ensure that stage #1 is on the bottom and stage #2 is on the top. If stage […]
Read more
This tip was a COMMENT on the sensible heat ratio tip left by Jim Bergmann. As usual, Jim makes a great point; once you get the “sensible” capacity for a piece of equipment at a set of conditions, you can easily calculate a true target delta T. Another interesting thing you can do is use […]
Read more